Your current location: HomeProducts & ServicesLV ProductsIntelligent type

Intelligent type

NYKW2 series intelligent air circuit breaker

It is mainly used to control and protect LV distribution network. which is normally installed in low-voltage power distribution cabinet for overall protection. Circuit breaker of no more than 1000A rated current could satisfy frequent start of electric motors.

  • AC rated current 630A~6,300A;
  • Short circuit breaking capacity 80kA~120kA(effective values);
  • Rated operating voltage AC690V and below;
  • 3-pole circuit breaker and 4-pole circuit breaker;
  • Drawer type circuit breaker and fixed type circuit breaker;
  • Reversible incoming installation;
  • Various intelligent controllers to realize different functions;
  • Isolation function, sign is"";
  • Carrying out IEC60947-2 and GB14048.2-2008 standards;
  • This circuit breaker has gained China Compulsion Certification "CCC".

NYKW3 series intelligent air circuit breaker

  • NYKW3-1250 series intelligent air circuit breaker (hereinafter referred to as circuit breaker) has features of compact structure, small volume, high reliability and zero arcing, etc.. Rated insulation voltage of circuit breaker is 690V, applying to AC 50Hz, 400V rated working voltage and 200A-1250A rated current. It’s mainly used in distribution network to distribute electricity, protect circuit and power supply equipment from over-load, under-voltage, short circuit and single-phase grounding fault hazards.
  • The circuit breaker is a three-dimensional arrangement, contact system of every phase is closed inside insulation base, forming a small independent chamber. These chambers constitute main circuit of circuit breaker.
  • Technical performance of circuit breaker conforms to standards of GB14048.2 Low-Voltage Switch Equipment and Controlling Equipment Low-Voltage Circuit Breaker and IEC60947-2 Low-Voltage Switch Equipment and Controlling Equipment Secondary Low-Voltage Circuit Breaker.

Main Specifications and Technical Parameters

Main Specifications and Technical Parameters of NYKW2 Series

Type NYKW2-2000
Frame grade rated current Inm (A) 2000
Rated current In(A) 630 800 1000 1250 1600 2000
Rated working voltage Ue(V) AC400,690 50Hz
Rated insulation voltage Ui(V) AC1000
Rated impulse withstand voltage Uimp(V) 12000
Power frequency withstand voltage (V) AC3500V 1min
Number of poles 3、4 3、4 3、4 3、4 3、4 3、4
Rated limit short-circuit breaking capacity Icu (kA) (Valid value) AC400V 85 85 85 85 85 85
AC690V 50 50 50 50 50 50
Rated operation short-circuit breaking capacity Ics (kA) (Valid value) AC400V 50 50 50 50 50 50
AC690V 40 40 40 40 40 40
Rated short-circuit making capacity Icm (kA) (peak) AC400V 176 176 176 176 176 176
AC690V 105 105 105 105 105 105
Rated short-time withstand current (1s) Icw (kA) (Valid value) AC400V 50 50 50 50 50 50
AC690V 40 40 40 40 40 40
Use category B
Full breaking time (no additional delay) (ms) 12-18
Closing time (ms) Max. 70
Intelligent controller Electronic type
Standard type
Communication type
Electrical life * (times) AC400V 10000 10000 10000 10000 10000 10000
AC690V 5000 5000 5000 5000 5000 5000
Mechanical life * (times ) Maintenance-free 10000 10000 10000 10000 10000 10000
Maintenance needed 20000 20000 20000 20000 20000 20000
Installation Overall Dimensions (mm) H W L H W L H W L H W L H W L H W L
Drawer type 3P 432 375 420 432 375 420 432 375 420 432 375 420 432 375 420 432 375 420
4P 432 470 420 432 470 420 432 470 420 432 470 420 432 470 420 432 470 420
Fixed type 3P 402 318 325 402 318 325 402 318 325 402 318 325 402 318 325 402 318 325
4P 402 413 325 402 413 325 402 413 325 402 413 325 402 413 325 402 413 325
NYKW2-3200 NYKW2-4000 NYKW2-6300
3200 6300
2000 2500 2900 3200 3600 4000 4000 5000 6300
AC400,690 50Hz
AC1000 50Hz
12000
AC3500V1min 50Hz
3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3
50%In、100%In
100 100 100 100 100 100 120 120 120
65 65 65 65 65 65 80 80 80
65 65 65 65 65 65 100 100 100
50 50 50 50 50 50 65 65 65
220 220 220 220 220 220 264 264 264
143 143 143 143 165 165 165 165 165
65 65 65 65 65 65 100 100 100
50 50 50 50 50 50 65 65 65
B
12-18
Max 70
10000 10000 10000 10000 10000 10000 500 500 500
5000 5000 5000 5000 5000 5000 500 500 500
10000 10000 10000 10000 10000 10000 2000 2000 2000
20000 20000 20000 20000 20000 20000 8000 8000 8000
H W L H W L H W L H W L H W L H W L H W L H W L H W L
432 435 420 432 435 420 432 435 420 432 435 420 432 550 493 432 813 493 432 813 493 432 928 493
432 550 420 432 550 420 432 550 420 432 550 420 432 788 493 432 928 493 432 928 493 — —
402 422 325 402 422 325 402 422 325 402 422 325 — — — — — — — —
402 515 325 402 515 325 402 515 325 402 515 325 — — — — — — — —

Main Specifications and Technical Parameters of NYKW3 Series

Type NYKW3-1250
Frame grade rated current Inm (A) 1250
Rated current In(A) 200 400 630 800 1000 1250
Rated working voltage Ue(V) AC400 50Hz
Rated insulation voltage Ui(V) AC690
Rated impulse withstand voltage Uimp(V) 6000
Power frequency withstand voltage (V) Main circuit AC2500
Number of poles 3、4 3、4 3、4 3、4 3、4 3、4
N phase rated current (A) 50%In、100%In
Rated limit short-circuit breaking capacity Icu (kA) (Valid value) AC400V 65 65 65 65 65 65
Rated operation short-circuit breaking capacity Ics (kA) (Valid value) AC400V 50 50 50 50 50 50
Rated short-time withstand current (1s) Icw (kA) (Valid value) AC400V 50 50 50 50 50 50
Full breaking time (no additional delay) (ms) 12-18
Closing time (ms) Max. 70
Electrical life * (times) AC400V 10000 10000 10000 10000 10000 10000
Mechanical life * (times ) Maintenance-free 10000 10000 10000 10000 10000 10000
Maintenance needed 20000 20000 20000 20000 20000 20000
Installation Overall Dimensions (mm) H W L H W L H W L H W L H W L H W L
Drawer type 3P 362 276 323 362 276 323 362 276 323 362 276 323 362 276 323 362 276 323
4P 362 346 323 362 346 323 362 346 323 362 346 323 362 346 323 362 346 323
Fixed type 3P 315 266 239 315 266 239 315 266 239 315 266 239 315 266 239 315 266 239
4P 315 336 239 315 336 239 315 336 239 315 336 239 315 336 239 315 336 239